G 19.3 N Uni-directional in-line detonation flame arrester, short-time burning proof

KITO® FD4-Det4-IIB1-…-1.2
KITO® FD4-Det4-IIB1-…-1.2-T

  • For installation into pipes to protect containers and components against stable detonation of flammable liquids and gases.
  • Tested and approved as detonation flame arrester type 4.
  • Approved for all substances of explosion groups IIA1 to IIB1 with a maximum experimental safe gap (MESG) ≥ 0.85 mm.
  • Working unidirectional in pipes, whereby an operating pressure of 1.2 bar abs. and an maximum operating temperature of 60 °C must not be exceeded.
  • Provided with one temperature sensor (PT 100) the armature is certified against short time burning from one side.
  • The installation is not dependent on the position and both directions of flow are possible.
  • During installation, please observe the direction of detonation and the indication „protected side“.