G 13 N Uni-directional in-line liquid detonation flame arrester

KITO® FL/E-…-IIB3

  • As inline armature, detonation-proof and flameproof, used for installation in filling and suction pipes outside from tanks in which in-flammable liquids are stored.
  • Tested and approved as detonation flame arrester type 4.
  • Approved for all materials of the explosion group IIA1 to IIB3 with MESG ≥ 0.65 mm and an maximum operating temperature of 60 °C.
  • Equipped with a safety device against complete emptying which is constructed as flame arrester element in order to prevent the suction of sealing liquid.
  • It is only allowed to install pipe of nominal widths ≤ than the nominal widths of the flange.
  • Mounting position is perpendicular.
  • The body of the housing has to be permanently filled with the storage liquid up to the height of the connecting flanges.
  • Suction rate V max specified in above table may not be exceeded.